Mecton — Blast Resistant Modules

Blast Resistant Modules

Hardened structures for oil, gas and petrochemical facilities, engineered to keep people protected and operations running when an explosion event occurs without warning.

10 PSI
Blast overpressure rating
200 ms
Certified pulse duration
API RP 752 & 753
Standards compliance
Sale & Hire
Immediate deployment
01 — Overview

What is a Blast-Resistant Module?

A Blast-Resistant Module (BRM) is a purpose-engineered structural unit designed to maintain its integrity — and protect its occupants — during an accidental explosion event at a process facility. Unlike conventional site cabins, every Mecton BRM is designed from the ground up to absorb and deflect overpressure loads defined by your site's risk assessment.

Our modules undergo rigorous physical blast testing and are rated to a Medium Response classification — sustaining 10 PSI at 200 milliseconds duration without structural failure or occupant injury. Each unit is designed in line with API RP 752 and API RP 753.

Key Capabilities
Proven and successfully blast-tested design
Immediate deployment from maintained ready fleet
Bespoke layouts and mission-specific configurations
Combinable units for larger hardened complexes
Ballistic and blast multi-threat protection available
Fully compliant with API RP 752 and API RP 753
02 — Module Types

Every Function. Hardened.

From muster refuge to daily working office, Mecton delivers blast protection across your entire facility footprint.

Refuge Shelters & Bunkers

Primary muster-point protection engineered to keep personnel safe during blast events on hazardous process facilities.

Office Modules

Fully habitable hardened workspaces providing blast-resistant accommodation without compromising operational productivity.

Laboratories

Precision-engineered protected environments for analytical and testing operations in high-risk process zones.

Workshops

Heavy-duty hardened workshop facilities for maintenance operations in close proximity to live process equipment.

Security Buildings

Access control and guard facilities engineered for perimeter security in petrochemical and industrial plants.

Portable Storage

Protected storage for sensitive equipment and critical materials in hazardous operational environments.

03 — Technical Specifications

Performance by the Numbers.

Response Rating
Medium
Structural classification
Blast Pressure
10 PSI
Peak overpressure
Load Duration
200 ms
Pulse duration
Standard
API RP 752
Siting of facilities
Standard
API RP 753
Portable structures
Widths
8 & 12 ft
Multiple lengths
04 — Features & Benefits

Built In, Not Bolted On.

Every Mecton BRM ships with the structural hardening and interior fit-out already built in — from steel-gauge wall panels to fire and life-safety systems — so the unit is ready to occupy the day it arrives on site.

  • Steel floor, wall and ceiling members covered with minimum 10-gauge steel panels
  • Two steel-reinforced doors
  • ISO lift and tie-down points at each corner
  • 9mm painted Calcium Silicate Board (CSB) wall lining and ceiling panels
  • PVC vinyl flooring sheet
  • Shielded fluorescent overhead lighting
  • Rockwool insulation
  • Standard RJ-45 / RJ-11 phone and Ethernet jacks
  • Single multi-cable transit for incoming electrical and communication services
  • HVAC system suitable for ambient use up to 52°C
  • Smoke detectors and ABC fire extinguishers
  • Exit signs with emergency lighting
05 — Technical Specifications

12ft Wide Module — Layout Options.

Size
Description
Response Level
3.6m x 12m (12' x 40')
Open Floor
460 square feet of open space, suited to anything from office space to a break room.
Low / Medium
3.6m x 12m (12' x 40')
One & Two Walls
Separate entrances for office space and storage within the same unit.
Low / Medium
3.6m x 12m (12' x 40')
One Wall with Restroom
Private office space, storage or a conference room, paired with restroom facilities.
Low / Medium
3.6m x 12m (12' x 40')
Restroom
Separate spaces for men and women, with sinks, toilets and urinals plumbed to a single wet wall.
Low / Medium
06 — Full Technical Specification

Standard 40ft x 12ft Module.

Product Description
  • 10 PSI at 200 ms blast-rated module
  • Medium Response classification as per ASCE
  • Approximate weight: 25,000 kg
External Dimensions
  • L 12.192 m x W 3.650 m x H 2.900 m
Hazardous Area Classification
  • All electrical fixtures mounted outside the module are Ex-rated
  • All electrical fixtures inside the module are rated for safe-area use
Structural
  • Primary members, walls, floor and roof engineered to withstand 10 PSI at 200 ms
  • S355-grade steel used for the primary structure
  • A36-equivalent grade steel used for secondary structure, wall plates, roof plates and floor plates
Pad Eyes
  • Designed and manufactured to industry two-point lifting requirements
Doors & Windows
  • Two 10 PSI blast-resistant exterior steel doors
  • No windows fitted
Insulation
  • Walls, floor and roof insulated to achieve a one-hour fire rating
Interior Finishes
  • Wall — 30 mm thick sandwich lining panels, secured to the steel structure with the necessary fixing profiles and fasteners
  • Ceiling — 0.7 mm thick GI folded tray ceiling system, secured to the steel structure with the necessary fixing profiles and fasteners
  • Floor — 12+18 mm thick cement fibre subfloor fixed to the structural steel, finished with a 2 mm vinyl mat and 100 mm high PVC skirting
Slings & Shackles
  • Not included
Electrical Input
Electrical Power
  • Incoming power supply of 220–690V, 50/60Hz, 3 phase + N + E
  • One 15kVA transformer included (3Ph 220–690V / 400V star, IP42; primary 220/400/440/460/480/690V 3P+N+E star, secondary 400V 3P+N+E star)
Incoming Power Isolator
  • One 40A incoming power isolator switch fitted outside the module
Distribution Panel
  • One distribution board in a steel enclosure, 415V 3 phase + N
Internal & Emergency Lighting
  • Surface-mounted 18W LED ceiling lights
  • Two 8W LED emergency exit lights
External Lighting
  • Two Ex-rated external lights fitted above each door, switch-controlled from inside (end modules only)
Outlets & Switches
  • Seven 2G 13A 230V switched sockets
  • One 1G 13A 230V socket
  • Two 2G 2W 10A switches
Internal Circuit & Cabling
  • Internal circuit runs concealed within GI cable trunking
  • Multicore PVC cabling sized to the detailed electrical design
All electrical fixtures inside the unit are rated for safe-area use; all fixtures outside the unit are Ex-rated.
Communication
  • Three 2 x RJ45 connection data outlets
  • One explosion-proof network junction box
  • One 8-port patch panel
HVAC
  • Wall-mounted split AC (2-ton duty + 2-ton standby), indoor unit suitable for safe-area application, 220–240V/1Ph/50–60Hz supply
  • Indoor unit houses two compressors and two direct-driven blower fans with CE-marked motors and a double-circuit evaporative coil
  • Condenser fan and coil installed in an external recess area of the module; condenser fan is Ex-rated
  • Evaporator and condenser coils constructed from copper tube with aluminium fins
Detection & Alarms
  • Two optical smoke detectors (conventional type)
  • Two manual call points
  • One fire alarm bell
  • Fire alarm panel (conventional type)
PAGA / Telephone
  • Not included
Painting
Exterior
  • Sandblasted to SA 2.5 (equivalent to SSPC 10)
  • 1st coat: Barrier 86 or equal, 50µ DFT
  • Final coat: Hard Top AS (white), 130µ DFT
Interior
  • 1 coat Barrier 86 or equal, 50µ DFT
Signage
  • All electrical equipment labelled
Testing
  • Quality assurance system in conformity with ISO 9001
  • Quality control and test reports provided with every unit